Nine years ago we bought a 22Kw Generac generator. Four years after that, the Plenum was leaking. It had to be replaced. Ever since then, the generator had difficulty starting during its weekly exercise. The motor would not start until during the second cracking cycle. Each time thereafter, it started correctly during the first cycle. But then, it would have difficulty starting four to five days thereafter. The company servicing our generator had us replace the battery, the gas pressure regulator to the generator, and we even had a larger gas meter installed. With my wife working remotely at home, she and I were concerned that this issue would get worse to the point where it would not start, specifically during a power outage.
I called Eau Gallie Electric in May this year for a maintenance service call, and I explained the issue to the tech. The difficulty with troubleshooting the issue and after making any changes is that once the generator starts, you have to wait at least a week to see if the situation is corrected. Over the next four months, a tech would come to the house on the day of the exercise for collecting gas pressure data. (One of the guys called our generator a Unicorn since the issue is unique because they have never seen this).
The guys finally came up with a plan to diagnostic/swap parts. They found the lower half of the mixer gasket half twisted over the second fuel port. Three of the four valve clearances were out of spec. The most astounding thing found was that the plenum that had been installed five years ago was the wrong one (it is for a 15KW generator). Also, the gas pipe to the plenum was very loose and could be turned my hand.
The first exercise after the repairs, the motor started up 5 seconds after the cranking started. The second exercise after the repair, the motor started up without struggling, 3 seconds after the cranking started. The generator sounds new. Kudos to everyone you worked/assisted with fixing the issue! Thank you Eau Gallie Electric!!